Arial Bundled Cable

Original
price: Negotiable
minimum:
Total supply:
Delivery term: The date of payment from buyers deliver within days
seat: Zhejiang
Validity to: Long-term effective
Last update: 2022-07-12 20:02
Browse the number: 226
inquiry
Company Profile
 
 
Product details

Self-supporting LV-ABC Cables(Franch Standard)

Aluminium conductors with XLPE insulation,standards:NFC 33-209

Dimensions of conductors



Cross section(mm²)


Stranded

DC resistance Ω/km

Conductor diameter


Thickness of insulation (mm)

Core diameter

carrying capacity

(A)


Breaking load (kN)

Min.(mm)

Max.(mm)

Min.(mm)

Max.(mm)

16

7

1.91

4.6

5.1

1.2

7.0

7.8

-

1.9

25

7

1.20

5.8

6.3

1.4

8.6

9.4

112

3.0

35

7

0.868

6.8

7.3

1.6

10.0

10.9

138

-

50

7

0.641

7.9

8.4

1.6

11.1

12.0

168

-

70

12

0.443

9.7

10.2

1.8

13.3

14.2

213

-

95

19

0.320

11.0

12.0

1.8

14.6

15.7

258

-

120

19

0.253

12.0

13.1

1.8

15.6

16.7

306

-

150

19

0.206

13.9

15.0

1.7

17.3

18.6

344

-


Dimensions of Neutral conductors

Cross section(mm²)

Conductor structure No./mm

DC resistance Ω/km


Conductor outer direction

Conductor diameter


Thickness of insulation

(mm)

Core diameter


Breaking load (kN)

Min.(mm)

Max.(mm)

Min.(mm)

Max.(mm)

54.6

7/3.15

0.63



left-hand

9.2

9.6

1.6

12.3

13.0

16.6

70

7/3.50

0.50

10.0

10.2

1.5

12.9

13.6

20.5

95

19/2.50

0.343

12.2

12.9

1.6

15.3

16.3

27.5

Test line


Cross section(mm²)


Stranded


DC resistance Ω/km


Conductor outer direction

Conductor diameter


Thickness of insulation

(mm)

Core diameter


Breaking load (kN)

Min.(mm)

Max.(mm)

Min.(mm)

Max.(mm)

1.5

1

12.1

-

-

1.5

1.2

3.7

4.2

-

PRODUCT TEST REPORT

Description

ABC CABLE

specification

ABC 3*50+54.6



Standar

NFC 33 209



Quantity

KM

No.

Properties

Standard requirements



Unit



Test results



Determine



Determine

1

Manufacturer

LAURENCE


LAURENCE

-

2

Nominal voltage(U0/U)

0.6/1

kV

0.6/1

-

3

Phase

3.1

Number of cores

1


1

Visual measurement

3.2

Cross section

50

mm²

50

-

3.3

Diameter of conductor

8.1±1%

mm

8.2

Vernier caliper

3.4

Nominal Thicknes

1.6

mm

1.7

Projector

3.5

Minimum Thicknes

1.34

mm

1.45

Projector

3.6



diameter of core

11.5

mm

11.6

Vernier caliper

3.7

resistance at 20 ℃.max

0.641

Ω/km

0.630

DC bridge

4

Neutral

4.1

Conductor structure

7/3.15

No./mm

7/3.15

Visual measurement

4.2

Diameter of AL wire

3.15±1%

mm

3.16

Micrometer

4.3

Diameter of conductor

9.45±1%

mm

9.45

Vernier caliper

4.4

Nominal Thicknes

1.6

mm

1.7

Projector

4.5

Minimum Thicknes

1.34

mm

1.47

Projector

4.6

diameter of core

12.65

mm

12.70

Vernier caliper

4.7

Rated Strength

16600

N

16693

Tensile testing machine

4.8

DC resistance at 20 ℃.max

0.63

Ω/km

0.60

DC bridge

5

Cable

5.1

diameter of bundle

28.3±1%

mm

28.5

Vernier caliper

5.2

Laying up direction

Right


Right

Visual measurement

5.3

Lay

430~590

mm

500

Ruler

5.4

Voltage test

3.5kV/5min

kV

3.5kV/5min

AC voltage test system

Results

Comply with standard and allow shipment.

http://www.laurence-group.com/